DARTMOUTH COLLEGE DESIGN

January 3, 2012 & CONSTRUCTION GUIDELINES 15890-METAL DUCTWORK & ACCESSORIES

Page 1 of 9

SECTION 15890

METAL DUCTWORK AND ACCESSORIES

PART 1 DESIGN DIRECTIVE

1.1 CODES AND QUALIFICATIONS

A.Firms regularly engaged in manufacture of metal ductwork, products and accessories of types, materials, and sizes required, whose products have been in satisfactory use in similar service for not less than 3 years.

B.Duct Leakage Test Manual

C.d for Ventilation Control and Fire Protection of Commercial Cooking Operations".

D.

E.Comply with the currently enforced edition of the International Mechanical Code for fabrication of metal ductwork.

F.



G.Comply with the North American Insulation Manufacturer's Association, "Fibrous Glass Duct Liner Standard", First Edition.

1.2 SUBMITTALS

A.

Submit ductwork Fabrication Shop Standards Manual indicating gauges, reinforcing, and similar information for ductwork, fittings, accessories, etc., for the required sizes and static pressure clasreview well in advance of sheet metal installation.

1.3 DELIVERY, STORAGE, AND HANDLING

A.

Store ductwork and accessories inside, above grade, and enclose with waterproof wrapping.

1.4 DESIGN CRITERIA

A.Low static pressure classifications shall be constructed to minimum 2" water gauge.

B.Medium static pressure classifications shall be constructed to minimum 5" water gauge.

C.



D.Ceiling registers shall be designed for one, two, three, or four way blow to suit room conditions.

The design documents shall indicate the flow directions.DARTMOUTH COLLEGE DESIGN

January 3, 2012 & CONSTRUCTION GUIDELINES 15890-METAL DUCTWORK & ACCESSORIES

Page 2 of 9

E.

The design documents shall indicate the clear inside dimensions of lined or double wall ducts.

F.

The designer shall determine the type of sealant required for the project and include in the specifications.

G.systems.

Refer to DC Standard 15010 for the requirements to determine the appropriate system for the project.

H.With respect to rectangular ductwork, the ratio of duct height to duct width shall not exceed 2:1.

In extraordinary conditions, this ratio may be extended to 2.5:1.

I.The designer shall determine if duct testing is required.

J.

The designer shall determine if the ductwork is to be painted and if so, amend the specifications to include a finish on the sheet metal that will accept field painting.

K.

This standard assumes standard galvanized duct for air distribution systems.

The designer is required to ascertain the suitability of this product for extraordinary applications, such as fume hoods, swimming pool ventilation, etc.

L.Two types of control dampers are specified.

For applications where dampers are exposed to outside air, and are normally closed 75% of the time or have a life safety requirement of not freezing in a position, use the insulated damper.

For all other dampers use the non-insulated damper.

M.All main electric rooms that are ventilated shall have filtered (30% efficiency) air.

N.All return air shall be ducted, plenum return is not acceptable.

PART 2 PRODUCTS

2.1 DUCTWORK MATERIALS

A.Galvanized sheet metal shall comply with ASTM A 924, lock forming quality, with G60 zinc coating for interior, dry duct and G90 zinc coating for exterior ducts and any ductwork susceptible to moisture, in accordance with ASTM A 653.

2.2 RECTANGULAR DUCT FABRICATION

A.Except as otherwise indicated, fabricate rectangular ducts with galvanized sheet steel, in 1-3 through 1-20, including associated details.

Conform to the requirements in the referenced standard for metal thickness, reinforcing types and intervals, tie rod applications, and joint types and intervals.

Minimum duct gauge is 26.

B.Cross break or bead duct sides that are 11" and larger and are 20 gauge or less, with more than 4 Figure 1-8, regardless if insulated.

C.Fabricate elbows, transitions, offsets, branch connections, and other duct construction in Figures 2-1 through 2-9, with the following modifications:

DARTMOUTH COLLEGE DESIGN

January 3, 2012 & CONSTRUCTION GUIDELINES 15890-METAL DUCTWORK & ACCESSORIES

Page 3 of 9 1.Figure 2-2 a
smacna duct construction standards pdf
Duct Construction Standards - Building Materials, Products ...
Section VII of the SMACNA HVAC Duct Construction Standards, 2nd ed., 1995. Certified copies of these tests are available upon request. (utexas.edu)
5.23.31 – Hvac Ducts Design And Construction Standard
with SMACNA's "HVAC Duct Construction Standards, Metal and Flexible". 2. ASHRAE Standards: Comply with ASHRAE Fundamentals Handbook (utexas.edu)
Dartmouth College Design January 3, 2012 & Construction …
B. Comply with SMACNA “HVAC Duct Construction Standards, Metal and Flexible, Second Edition (1995)” for fabrication and installation of metal ductwork. (utexas.edu)
.Type RE1 Square throat is not permitted.b.

Types RE4, 6, 7, 8, 9, & 10 are not permitted.

2.Figure 2-3 a.Use single thickness vanes with 4--

3.Figure 2-7 a.

Offset types 1& 2 are not allowed.b.Minimum bell mouth radius shall be 1-

4.

Figure 2-8 a.

Figures A & C are not allowed.

D.Fabricate duct fittings to match adjoining ducts, and to comply with duct requirements as applicable to fittings.Limit angular tapers to 30 for contracting tapers and 20 for expanding tapers.

E.Button punch snap lock (figure 1-5, type L-2) and internal standing seam joints (figure 1-6) are not allowed.

2.3 ROUND DUCT FABRICATION

A.Except as otherwise indicated, fabricate round ducts with galvanized sheet steel, in accordance -1 through 3-3 and figures 3-1 through 3-5.

Conform to the requirements in the referenced standard for metal thickness and joint types.

Modify the above tables and figures as follows:

1.

Table 3-1 a.All elbows, regardless of duct velocity, shall be 1-1/2" radius to duct diameter.

2.Figure 3-1 a.

Seam types RL-3, 6A, 6B, 7, and * are not allowed.

3.Figure 3-3 a.Adjustable elbows are not allowed.

4.

Figure 3-4 a.

Non lateral taps may be used only where spatial conditions do not allow lateral taps.

5.Figure 3-5 a.Replace the transition length formula listed (L2=A-B) with the following: Limit angular tapers to 30 for contracting tapers and 20 for expanding tapers.

B.Fittings shall be one gauge heavier than the duct size requirement, 22 gauge minimum.

2.4 HANGERS AND SUPPORTS

A.Except as otherwise indicated, fabricate hangers and supports in accordance with SMACNA chapter as follows:

1.

Powder actuated fasteners are not allowed.

2.Wire is not allowed to be used as a hanger support.

DARTMOUTH COLLEGE DESIGN

January 3, 2012 & CONSTRUCTION GUIDELINES 15890-METAL DUCTWORK & ACCESSORIES

Page 4 of 9 2.5 DOUBLE WALL DUCTWORK

A.Construct double wall ductwork with a solid outer skin, gauge and reinforcement shall be as previously specified for single wall ductwork.

Insulation shall be 1" thick duct liner.

Inner skin shall be 26 gauge perforated galvanized steel.

2.6 DAMPERS

A.

Provide manual dampers of single blade type or multi blade type, constructed in accordance with -12 and 2-13, amended as follows:

1.Figure 2-12 a.Figure A is not allowed, use only figure B regardless of duct size.b.Provide end bearings for all systems requiring Seal Class A regardless of pressure class.

B.Provide galvanized steel control dampers with parallel blades for two position control, opposed blades for modulating control.

Provide counterbalanced relief dampers with parallel blades, counterbalanced and factory set to relieve at indicated static pressure.

C.

Subject to compliance with requirements, provide dampers of one of the following: 1.Air Balance, Inc.2.

American Warming & Ventilating, Inc.3.Arrow Louver and Damper; Div.

of Arrow United Industries, Inc.4.Louvers & Dampers, Inc.

5.Ruskin Mfg.Co.6.Vent Products Co., Inc

D.Insulated dampers shall be constructed of aluminum with expanded polyurethane blades (R=2.2 min.) and a thermally broken, polystyrene filled frame.

Blade & frame seals shall be extruded Dampers shall be manufactured to the actual opening, do not safe off the opening to use stock sizes.

E.Subject to compliance with requirements, provide dampers of one of the following: 1.Tamco series 9000 BF.

2.7 FIRE DAMPERS

A.Curtain type fire dampers constructed with casings of 20-22 galvanized steel with fusible link rated at 212F.

Test all dampers in accordance with UL555.

Curtain must be completely out of the air stream when damper is open.

All dampers must be dynamic rated for design class of the duct system and the air velocity.

Rating of fire damper shall be compatible with the rating of the building structure (wall or ceiling) in which it is installed.

B.

Subject to compliance with requirements, provide dampers of one of the following: 1.Air Balance, Inc.2.American Warming & Ventilating, Inc.

3.Greenheck 4.Prefco Products

5.Ruskin Mfg.

Co.

DARTMOUTH COLLEGE DESIGN

January 3, 2012 & CONSTRUCTION GUIDELINES 15890-METAL DUCTWOR.
5.23.31hvacducts
.